Georgia Researchers Develop Cooling Strategies


June 3 -- Approximately a third of the electricity consumed by large datacenters doesn't power the computer servers that conduct online transactions, serve Web pages or store information. Instead, that electricity must be used for cooling the servers, a demand that continues to increase as computer processing power grows. And the trend toward cloud computing will expand the need for both servers and cooling.

At the Georgia Institute of Technology, researchers are using a 1,100-square-foot simulated datacenter to optimize cooling strategies and develop new heat transfer models that can be used by the designers of future facilities and equipment. The goal is to reduce the portion of electricity used to cool datacenter equipment by as much as 15 percent.

"Computers convert electricity to heat as they operate," said Yogendra Joshi, a professor in Georgia Tech's Woodruff School of Mechanical Engineering. "As they switch on and off, transistors produce heat, and all of that heat must be ultimately transferred to the environment. If you are looking at a few computers, the heat produced is not that much. But datacenters generate heat at the rate of tens of megawatts that must be removed."

Summaries of the research have been published in the Journal of Electronic Packaging and International Journal of Heat and Mass Transfer and presented at the Second International Conference on Thermal Issues in Emerging Technologies, Theory and Applications. The research has been sponsored by the U.S. Office of Naval Research, and by the Consortium for Energy Efficient Thermal Management.

Five years ago, a typical refrigerator-sized server cabinet produced about one to five kilowatts of heat. Today, high-performance computing cabinets of about the same size produce as much as 28 kilowatts, and machines already planned for production will produce twice as much.

"Some people have called this the Moore's Law of datacenters," observed Joshi, who is also the John M. McKenney and Warren D. Shiver Chair in the School of Mechanical Engineering. "The growth of cooling requirements parallels the growth of computing power, which roughly doubles every 18 months. That has brought the energy requirements of datacenters into the forefront."

Most existing datacenters rely on large air conditioning systems that pump cool air to server racks. Datacenters have traditionally used raised floors to allow space for circulating air beneath the equipment, but cooling can also come from the ceilings. As cooling demands have increased, datacenter designers have developed complex systems of alternating cooling outlets and hot air returns throughout the facilities.

"How these are arranged is very important to how much cooling power will be required," Joshi said. "There are ways to rearrange equipment within datacenters to promote better air flow and greater energy efficiency, and we are exploring ways to improve those."

Before long, centers will likely have to use liquid cooling to replace chilled air in certain high-powered machines. That will introduce a new level of complexity for the datacenters, and create differential cooling needs that will have to be accounted for in the design and maintenance.

Joshi and his students have assembled a small high-power-density datacenter on the Georgia Tech campus that includes different types of cooling systems, partitions to change room volumes and both real and simulated server racks. They use fog generators and lasers to visualize air flow patterns, infrared sensors to quantify heat, airflow sensors to measure the output of fans and other systems, and sophisticated thermometers to measure temperatures on server motherboards.

Beyond studying the effects of alternate airflow patterns, they are also verifying that cooling systems are doing what they're supposed to do. Because tasks are dynamically assigned to specific machines, heat generation varies in a datacenter. Joshi's group is also exploring algorithms that could help even out the computing load by assigning new computationally-intensive tasks to cooler machines, avoiding hot spots.

Another issue they're studying is what happens when utility-system power to a datacenter is cut off. The servers themselves continue to operate because they receive electricity from an uninterruptible power supply. But the cooling equipment is powered by backup generators, which can take minutes to get up to speed.

During the brief time without cooling, heat builds up in the servers. Existing computer models predict that temperatures will reach dangerous levels in a matter of seconds, but actual measurements done by Joshi's graduate students show that the equipment can run for as much as six minutes without cooling.

"We're developing models for different parts of the datacenter to learn how they respond to changes in temperature," said Shawn Shields, a former graduate student in Joshi's lab. "Existing models consider that temperature changes across a server rack will be instantaneous, but we've found that it takes quite a relatively long time for the server to reach a steady state."

Beyond reducing cooling load, the researchers are also looking at how waste heat from datacenters can be used. The problem is that the heat is at relatively low temperatures, which makes it inefficient to convert to other forms of energy. Options may include heating nearby buildings or pre-heating water, Joshi said.

Data obtained by the researchers with thermometers and airflow meters is being used to validate computer models that are reasonably accurate, but run rapidly. In the future, these models will help datacenter operators do a better job of optimizing cooling in real time, he said.

Joshi believes there's potential to reduce datacenter energy consumption by as much as 15 percent by adopting more efficient cooling techniques like those under development in his lab.

"Our datacenter laboratory is a complete sandbox in which we can study all sorts of options without affecting anybody's computing projects," he added. "We can look at interesting ways to improve rack-level cooling, liquid cooling and thermoelectric cooling."

-----

Source: John Toon, Georgia Institute of Technology

Sponsored Links

Accelerate your science with Seneca
One of the first HPC providers installing a 4X NVIDIA Kepler K-20 cluster. Invites you to a free evaluation on Seneca’s NVIDIA K20 Kepler cluster, pre-loaded with AMBER, NAMD, LAMMPS

High-Performance Computing in Action
Businesses that want to be on the cutting edge of their industries are increasingly turning to high-performance computing (HPC) solutions to handle complex compute processes and speed up their rate of innovation. Download this Executive Brief to see how businesses in energy, life sciences and entertainment put HPC solutions to work in their operations.

May 17, 2013

May 16, 2013

May 15, 2013

May 14, 2013

May 13, 2013

May 10, 2013

May 09, 2013

May 08, 2013

May 07, 2013

May 06, 2013


Cray CS300-LC

Feature Articles

Saddling Phi for TACC’s Stampede

The Xeon Phi coprocessor might be the new kid on the high performance block, but out of all first-rate kickers of the Intel tires, the Texas Advanced Computing Center (TACC) got the first real jab with its new top ten Stampede system.We talk with the center's Karl Schultz about the challenges of programming for Phi--but more specifically, the optimization...
Read more...

"No Exascale for You!" An Interview with Berkeley Lab's Horst Simon

Although Horst Simon was named Deputy Director of Lawrence Berkeley National Laboratory, he maintains his strong ties to the scientific computing community as an editor of the TOP500 list and as an invited speaker at conferences.
Read more...

Supercomputing Vet Champions Quantum Cause

Supercomputing veteran, Bo Ewald, has been neck-deep in bleeding edge system development since his twelve-year stint at Cray Research back in the mid-1980s, which was followed by his tenure at large organizations like SGI and startups, including Scale Eight Corporation and Linux Networx. He has put his weight behind quantum company....
Read more...

Short Takes

Running Computational Fluid Dynamics in the Cloud

May 16, 2013 | When it comes to cloud, long distances mean unacceptably high latencies. Researchers from the University of Bonn in Germany examined those latency issues of doing CFD modeling in the cloud by utilizing a common CFD and its utilization in HPC instance types including both CPU and GPU cores of Amazon EC2.
Read more...

Computing the Physics of Bubbles

May 15, 2013 | Supercomputers at the Department of Energy’s National Energy Research Scientific Computing Center (NERSC) have worked on important computational problems such as collapse of the atomic state, the optimization of chemical catalysts, and now modeling popping bubbles.
Read more...

Internet2 Awards Program Seeks Innovative Applications

May 10, 2013 | Program provides cash awards up to $10,000 for the best open-source end-user applications deployed on 100G network.
Read more...

Floating Funding to Exascale Island

May 09, 2013 | The Japanese government has revealed its plans to best its previous K Computer efforts with what they hope will be the first exascale system...
Read more...

HPC and the True Cost of Cloud

May 08, 2013 | For engineers looking to leverage high-performance computing, the accessibility of a cloud-based approach is a powerful draw, but there are costs that may not be readily apparent.
Read more...

Sponsored Whitepapers

Best Practices in Big Data Storage

05/10/2013 | Cleversafe, Cray, DDN, NetApp, & Panasas | From Wall Street to Hollywood, drug discovery to homeland security, companies and organizations of all sizes and stripes are coming face to face with the challenges – and opportunities – afforded by Big Data. Before anyone can utilize these extraordinary data repositories, however, they must first harness and manage their data stores, and do so utilizing technologies that underscore affordability, security, and scalability.

Progress in Parallel: the Bull Parallel Programming Center

04/15/2013 | Bull | “50% of HPC users say their largest jobs scale to 120 cores or less.” How about yours? Are your codes ready to take advantage of today’s and tomorrow’s ultra-parallel HPC systems? Download this White Paper by Analysts Intersect360 Research to see what Bull and Intel’s Center for Excellence in Parallel Programming can do for your codes.

Sponsored Multimedia

SGI DMF ZeroWatt Disk Solution

In this demonstration of SGI DMF ZeroWatt disk solution, Dr. Eng Lim Goh, SGI CTO, discusses a function of SGI DMF software to reduce costs and power consumption in an exascale (Big Data) storage datacenter.

Cray CS300-AC Cluster Supercomputer Air Cooling Technology Video

The Cray CS300-AC cluster supercomputer offers energy efficient, air-cooled design based on modular, industry-standard platforms featuring the latest processor and network technologies and a wide range of datacenter cooling requirements.

SC12 Editorial Feature HPCwire Soundbite sponsored by ISC

HPC Job Bank


Featured Events


  • June 16, 2013 - June 20, 2013
    ISC'13
    Leipzig,
    Germany

  • June 17, 2013 - June 18, 2013
    Forecast 2013
    San Francisco, CA
    United States





HPCwire Events